Setup
3.4 Inputs and outputs
FST030
114 Function Manual, 04/2017, A5E35693328-AA
3.4.4.2
Active operation (read only)
Description
Shows application possibilities.
Setting Active operation not possible, use passive wiring; Active operation possible, hardware is
able to drive the current loop
Default
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Active operation
3.4.4.3
Fail-safe activation condition
Description
Defines the condition the fail-safe behaviour of the channel becomes active and determines
the channel availability.
Setting
Invalid process value; Maintenance alarm or Failure (NAMUR)
Default
Maintenance alarm or Failure (NAMUR)
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Fail-safe activation condition
3.4.4.4
Current output
3.4.4.4.1 Process value
Description
Select process value for the current output.
Setting
Volume flow; Mass flow; Standard volume flow (only hydrocarbon and gas applications);
Flow velocity; Sound velocity; LiquIdent (only hydrocarbon applications); Density; Kinemat-
ic viscosity; Pressure; Medium temperature; Standard density (only hydrocarbon and gas
applications); Standard kinematic viscosity (only hydrocarbon applications); API gravity
(only hydrocarbon applications); Standard API gravity (only hydrocarbon applications);
Specific gravity (only hydrocarbon applications); Standard specific gravity (only hydrocar-
bon and gas applications); Auxiliary temperature; Sensor temperature; Standardizing factor
(only hydrocarbon and gas applications)
Default
Mass flow
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Process value