Setup
3.4 Inputs and outputs
FST030
170 Function Manual, 04/2017, A5E35693328-AA
3.4.7.5.7 Fail-safe behaviour
Description
Current output reaction in case of a fault.
Setting
Lower fault current; Upper fault current; Last valid value; Current value; Fail-safe value
Default
Lower fault current
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Current output → Fail-safe behav-
iour
3.4.7.5.8 Fail-safe value
Description
Output value in case of a fault and when fail-safe mode configured to Fail-safe value.
Setting
0.0 mA to 25.0 mA
Default
0.0 mA
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Current output → Fail-safe value
3.4.7.5.9 Fail-safe minimum time
Description
Minimum time the output stays in fail-safe mode.
Setting
0 s to 100 s
Default
0 s
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Current output → Fail-safe mini-
mum time
3.4.7.6
Frequency output
3.4.7.6.1 Process value
Description
Select process value for the frequency output.