Setup
3.2 Process values
FST030
Function Manual, 04/2017, A5E35693328-AA
67
Select units for displayed pressure. Units are not applied at communication interface.
Setting
mbar (millibar); bar; Pa (pascals); kPa (kilopascals); MPa (Megapascals); psi (pounds per
square inch); kgf/cm² (kilogram force per square cm); mmH2O (millimeters of water at 68
°F); inH2O (inches of water at 68 °F); ftH2O (feet of water at 68 °F); mmH2O (millimeters
of water at 4 °C); inH2O (inches of water at 4 °C); mmHg (millimeters of mercury at 0 °C);
inHg (inches of mercury at 0 °C); hPa (hectopascal); atm (atmosphere); torr; cmH2O (cen-
timeters of water at 4 °C); mH2O (meters of water at 4 °C); cmHg (centimeters of mercury
at 0 °C); mHg (meters of mercury at 0 °C); gf/cm² (grams force per square cm); kg/m² (kil-
ograms per square
meter); lb/ft² (pounds per square foot); ftH2O (feet water at 4 °C); ftH2O
(feet water at 60 °F)
Setup → Process values → Pressure → Units
Decimal places
Description
Sets the decimal places for the process value displayed in the local display.
Setting
Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal
places; 5 decimal places; 6 decimal places
Setup → Process values → Pressure → Decimal places
Alarm and warning limits
3.2.9.3.1 Upper alarm limit
Description
If process value exceeds this limit an alarm is triggered.
-9999997952 Pa to +9999997952 Pa