Setup
3.4 Inputs and outputs
FST030
120 Function Manual, 04/2017, A5E35693328-AA
Setting
Minimum frequency; Maximum frequency; Last valid value; Current value; Fail-safe value
Default
Last valid value
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Frequency output → Fail-safe behav-
iour
3.4.4.5.9 Fail-safe value
Description
Output value in case of a fault and when fail-safe mode configured to Fail-safe value.
Setting
0.0 Hz to 12500.0 Hz
Default
0.0 Hz
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Frequency output → Fail-safe value
3.4.4.5.10 Fail-safe minimum time
Description
Minimum time the output stays in fail safe mode.
Setting
0 s to 100 s
Default
0 s
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Frequency output → Fail-safe minimum
time
3.4.4.6
Pulse output
3.4.4.6.1 Process value
Description
Select process value for the pulse output.
Setting
Mass flow; Volume flow; Standard volume flow rate (only hydrocarbon and gas applica-
tions)
Default
Volume flow