Setup
3.2 Process values
FST030
48 Function Manual, 04/2017, A5E35693328-AA
Related
Path
Setup → Process values → Mass flow → Custom conversion factor
3.2.2.4
Decimal places
Description
Sets the decimal places for the process value displayed in the local display.
Setting Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal
places; 5 decimal places; 6 decimal places
Default
2 decimal places
Related
Path
Setup → Process values → Mass flow → Decimal places
3.2.2.5
Low flow cut-off
Description
Mass flow limit for low flow cut off. Below limit mass flow output is forced to zero.
Setting
0.00 to 3682800.00 kg/h (depends on sensor)
Default
0.1% of maximum mass flow (depends on sensor)
Related
Path
Setup → Process values → Mass flow → Low flow cut-off
3.2.2.6
Alarm and warning limits
3.2.2.6.1 Upper alarm limit
Description
If mass flow value exceeds this limit an alarm is triggered.
Setting
-3682800.00 kg/h to +3682800.00 kg/h
Default
3682800.00 kg/h
Related
Path
Setup → Process values → Mass flow → Alarm and warning limits → Upper alarm limit