Communication
5.3 Modbus (Channel 1)
FST030
320 Function Manual, 04/2017, A5E35693328-AA
Setting
0.0 to 100.0 s
Default
0.0 s
Related
Path
Communication → Modbus (Channel 1) → Damping → Damping value
5.2.9.2
Process values (1)
Description
Select the process values.
Setting
Volume flow; Mass flow; Totalizer 1; Totalizer 2; Totalizer 3; Sound velocity; Flow velocity;
Pressure; Kinematic viscosity; Standard volume flow; Standardizing factor; Standard kine-
matic viscosity; Standard density; LiquIdent; Density; Medium temperature
Default
Volume flow
Related
Path
Communication → Modbus (Channel 1) → Damping → Process values (1)
5.2.9.3
Process values (2)
Description
Select the process values.
Setting
API gravity; Standard API gravity; Specific gravity; Standard specific gravity; Rate of
change
Default
API gravity
Related
Path
Communication → Modbus (Channel 1) → Damping → Process values (2)
5.3
Modbus (Channel 1)
5.3.1
Slave address (SW)
Description
The
slave address (SW)
for the Modbus device can be configured. This address is used if
the DIP switch is set to 0.