Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
139
Setting
0 s to 100 s
Default
0 s
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Frequency output → Fail-safe
minimum time
3.4.5.6.11 Fail-safe value
Description
Output value in case of a fault and when fail-safe mode configured to fail-safe value.
Setting
0.0 Hz to 12500.0 Hz
Default
0.0 Hz
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Frequency output → Fail-safe
value
3.4.5.7
Pulse output
3.4.5.7.1 Redundancy mode
Description
Sets the redundancy mode. The pulses on channel 3 will follow pulses on channel 2 with 90°
or 180° shift.
Setting
Off. Channel 3 runs in independently; 90°. Channel 3 follows pulses on channel 2 with a
90° shift; 180°. Channel 3 follows pulses on channel 2 with a 180° shift
Default
Off. Channel 3 runs in independently
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Pulse output → Redundancy
mode
3.4.5.7.2 Process value
Description
Select process value for the pulse output.