Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
117
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Fail-safe behaviour
3.4.4.4.8 Fail-safe value
Description
Output value in case of a fault and when fail-safe behaviour configured to fail-safe value.
Setting 0.0 mA to 25.0 mA
Default
0.0 mA
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Fail-safe value
3.4.4.4.9 Fail-safe minimum time
Description
Minimum time the output stays in fail-safe mode.
Setting
0 s to 100 s
Default
0 s
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Fail-safe minimum
time
3.4.4.5
Frequency output
3.4.4.5.1 Process value
Description
Select process value for the frequency output.
Setting
Volume flow; Mass flow; Standard volume flow (only hydrocarbon and gas applications);
Flow velocity; Sound velocity; LiquIdent (only hydrocarbon applications); Density; Kinemat-
ic viscosity; Pressure; Medium temperature; Standard density (only hydrocarbon and gas
applications); Standard kinematic viscosity (only hydrocarbon applications); API gravity
(only hydrocarbon applications); Standard API gravity (only hydrocarbon applications);
Specific gravity (only hydrocarbon applications); Standard specific gravity (only hydrocar-
bon and gas applications); Auxiliary temperature; Sensor temperature; Standardizing factor
(only hydrocarbon and gas applications)
Default
Volume flow