Setup
3.4 Inputs and outputs
FST030
118 Function Manual, 04/2017, A5E35693328-AA
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Frequency output → Process value
3.4.4.5.2 Direction
Description
Flow direction filter applicable for process values mass flow/volume flow/flow
velocity/standard volume flow rate (only hydrocarbon and gas applications).
Setting Positive; Negative; Bidirection; Bidirectional (symmetric)
Default
Positive
Related
Path
Setup → Inputs and outputs → Channel 2 -output → Frequency output → Direction
3.4.4.5.3 Frequency value high
Description
Upper frequency value. Upper nominal output range boundary.
Setting
0.0 Hz to 12500.0 Hz
Default
10000.0 Hz
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Frequency output → Frequency value
high
3.4.4.5.4 Frequency value low
Description
Lower frequency value. Lower nominal output range boundary.
Setting
0.0 Hz to 12500.0 Hz
Default
0.0 Hz
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Frequency output → Frequency value
low