Setup
3.2 Process values
FST030
Function Manual, 04/2017, A5E35693328-AA
51
Setting
-
Default
1.0
Related
Path
Setup → Process values → Standard volume flow → Custom conversion factor
3.2.3.4
Decimal places
Description
Sets the decimal places for the process value displayed in the local display.
Setting
Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal
places; 5 decimal places; 6 decimal places
Default
2 decimal places
Related
Path
Setup → Process values → Standard volume flow → Decimal places
3.2.3.5
Low flow cut-off
Description
Standard volume flow limit for low flow cut off. Below limit standard volume flow output is
forced to zero.
Setting
Min. 0.0 Sm
3
/s
Default
0.0 Sm
3
/s
Related
Path
Setup → Process values → Standard volume flow → Low flow cut-off
3.2.3.6
Alarms and warning limits
3.2.3.6.1 Upper alarm limit
Description
Exceeding this limit causes an alarm.
Setting
-10800000.00 Sm
3
/h to +10800000.00 Sm
3
/h
Default
3600.00 Sm
3
/h