Setup
3.2 Process values
FST030
Function Manual, 04/2017, A5E35693328-AA
53
3.2.3.6.5 Hysteresis
Description
Hysteresis that affects the alarm and warning limits.
Setting
-10800000.00 Sm
3
/h to +10800000.00 Sm
3
/h
Default
0.00 Sm
3
/h
Related
Path
Setup → Process values → Standard volume flow → Alarm and warning limits → Hysteresis
3.2.3.7
Standard temperature
Description
Standard temperature - This value is used to calculate the standard process values.
Setting
0.0 °C (32 °F) to 100.0 °C (212.0 °F)
Default
15.0 °C (59.0 °F)
Related
Path
Setup → Process values → Standard volume flow → Standard temperature → Units
3.2.3.8
Standard pressure
Description
Standard pressure - This value is used to calculate standard process values.
Setting
100000.0 Pa to 200000.0 Pa
Default
101325.0 Pa (pascal)
Related
Path
Setup → Process values → Standard volume flow → Standard pressure
3.2.3.9
Air density at standard conditions
Description
Air density at standard conditions. This value is used to calculate standard process values.
Setting
0.01 kg/m³ to 10.0 kg/m³
Default
1.0 kg/m³