Maintenance and diagnostics
4.5 Peak values
FST030
Function Manual, 04/2017, A5E35693328-AA
275
Related
This parameter is only available if
Process value
is
not
set to Disabled.
Path Maintenance and diagnostics → Peak values → Process value 1 → Maximum value
timestamp
4.5.1.4
Minimum
Description
Displays minimum measured value.
Related
This parameter is only available if
Process value
is
not
set to Disabled.
Path Maintenance and diagnostics → Peak values → Process value 1 → Minimum value
4.5.1.5
Timestamp at minimum value
Description
Displays the timestamp when minimum value was measured.
Related
This parameter is only available if
Process value
is
not
set to Disabled.
Path
Maintenance and diagnostics → Peak values → Process value 1 → Minimum value
timestamp
4.5.1.6
Reset peak values
Description
This command is used to reset the logging of the recorded maximum and minimum values
monitored. The drag pointers will be set to the current value.
Setting
Cancel; Ok
Default
Cancel
Related
This parameter is only available if
Process value
is
not
set to Disabled.
Path
Maintenance and diagnostics → Peak values → Process value 1 → Reset logging