Maintenance and diagnostics
4.8 Simulation
FST030
Function Manual, 04/2017, A5E35693328-AA
291
4.8.1.5.3 Simulation value
Description
Set the current value to be output on the channel when current output or current input
simulation is enabled.
Set the frequency value to be output on the channel when frequency output simulation is
enabled.
Set the pulse value to be output on the channel when pulse output simulation is enabled.
Set the signal level to be output on the channel when status output or digital input simulation
is enabled.
Setting
0 mA to 25 mA
Default
0 mA
Operation mode is set to Current output or Current input
Setting
0.0 Hz to 12500.0 Hz
Default
1.0 Hz
Operation mode is set to Frequency output
Setting
0.0 pulses/s to 12500.0 pulses/s
Default
0.0
Operation mode is set to Pulse output
Setting
0; 1
Default
0
Operation mode is set to Status output or Digital input
Related
Only if parameter
Simulation
is set to Enabled, then the setting of this parameter
will be
relevant.
Path
Maintenance and diagnostics → Simulation → Simulation inputs and outputs → Channel 4 -
input/output → Simulation value
4.8.1.6
Channel 4 - relay
4.8.1.6.1 Simulation
Description
Enables or disables simulation of channel 4 relay output.