Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
187
3.4.7.10
Current input
3.4.7.10.1 Process value
Description
Assignments of the current input value to a process value.
Read only.
Setting Off; Pressure; Density; Kinematic viscosity; Medium temperature; Sensor temperature
(current input) Auxiliary temperature (current input)
Default
Off
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Current input → Process value
3.4.7.10.2 Change process value
Description
Change process value - selection enable the changing of the process value
Setting
Off; Pressure; Medium temperature; Density; Kinematic viscosity; Sensor temperature;
Auxiliary temperature
Default
Off
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Current input → Change process
value
3.4.7.10.3 Loop current scale
Description
Loop current scale - Selects current input scaling according to desired measurement range
and fail-safe mode.
Setting
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR;
4 to 20 mA (3.75) 4.0 to 20.8 (22.6) US;
4 to 20 mA (0.00) 4.0 to 20.5 (22.0);
4 to 20 mA (2.00) 4.0 to 24.0 (25.0);
0 to 20 mA (0.00) 0.0 to 20.5 (22.0);
0 to 20 mA (0.00) 0.0 to 24.0 (25.0)
Default
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR