Setup
3.2 Process values
FST030
Function Manual, 04/2017, A5E35693328-AA
45
Related
Path
Setup → Process values → Volume flow → Custom conversion factor
3.2.1.4
Decimal places
Description
Sets the decimal places for the process value displayed in the local display.
Setting Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal
places; 5 decimal places; 6 decimal places
Default
2 decimal places
Related
Path
Setup → Process values → Standard volume flow → Decimal places
3.2.1.5
Low flow cut-off
Description
Volume flow limit for low flow cut off. Below limit volume flow output is forced to zero.
Setting
0.00 m
3
/h to 896.40 m
3
/h (depends on sensor)
Default
0.1% of maximum flow (depends on sensor)
Related
Path
Setup → Process values → Volume flow → Low flow cut-off
3.2.1.6
Alarm and warning limits
3.2.1.6.1 Upper alarm limit
Description
Set Upper alarm limit. Alarm is triggered if measured value is above the limit.
Setting
-896.40 m
3
/h to 896.40 m
3
/h
Default
896.40 m
3
/h
Related
Path
Setup → Process values → Volume flow → Alarm and warning limits → Upper alarm limit