Setup
3.4 Inputs and outputs
FST030
116 Function Manual, 04/2017, A5E35693328-AA
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Upper range value
3.4.4.4.5 Lower range value
Description
Sets value at 0% of measuring span and corresponds to a loop current of 0/4 mA.
Setting and Default are sensor specific, depending on the setting in Process value and
depending on the Units setting.
Setting -3682800.00 kg/h to +3682800.00 kg/h
Default
0.00 kg/h
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Lower range value
2.4.4.4.6 Damping value
Description
Sets the Damping (filtering) to smooth out response to sudden changes in measurement.
An increase to Damping value increases response time of device, and affects digital value
and loop current. If output values are noisy, increase Damping value. For faster response
time, decrease Damping value. Find a value that meets requirements of signal stability and
response time.
Setting
0.00 s to 100.00 s
Default
0.00 s
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Current output → Damping value
3.4.4.4.7 Fail-safe behaviour
Description
Current output reaction in case of a fault.
Setting
Lower fault current; Upper fault current; Last valid value; Current value; Fail-safe value
Default
Lower fault current