Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
171
Setting
Volume flow; Mass flow; Standard volume flow (only hydrocarbon and gas applications);
Flow velocity; Sound velocity; LiquIdent (only hydrocarbon applications); Density; Kinemat-
ic viscosity; Pressure; Medium temperature; Standard density (only hydrocarbon and gas
applications); Standard kinematic viscosity (only hydrocarbon applications); API gravity
(only hydrocarbon applications); Standard API gravity (only hydrocarbon applications);
Specific gravity (only hydrocarbon applications); Standard specific gravity (only hydrocar-
bon and gas applications); Auxiliary temperature; Sensor temperature; Standardizing factor
(only hydrocarbon and gas applications)
Default
Volume flow
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output (4) → Frequency output → Process
value
3.4.7.6.2 Direction
Description
Flow direction filter applicable for process values mass flow/volume flow/flow
velocity/standard volume flow rate (only hydrocarbon and gas applications).
Setting
Positive; Negative; Bidirectional; Bidirectional (symmetric)
Default
Positive
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Frequency output → Direction
3.4.7.6.3 Frequency value high
Description
Upper frequency value. Upper nominal output range boundary.
Setting
0.0 Hz to 12500.0 Hz
Default
10000.0 Hz
Related
Path
Setup → Inputs and outputs → Channel 4 - input/output → Frequency output → Frequency
value high
3.4.7.6.4 Frequency value low
Description
Lower frequency value. Lower nominal output range boundary.