Maintenance and diagnostics
4.4 Diagnostics
FST030
272 Function Manual, 04/2017, A5E35693328-AA
If
is set to Status output, this parameter will show the status output value.
Path Maintenance and diagnostics → Diagnostics → Inputs and outputs → Channel 4 - in-
put/output → Channel value
4.4.3.5.3 Error status (read only)
Description
The error status of the channel can be viewed in this parameter.
Options Overflow; Underflow; Fail-safe behaviour activated; Cable break; Output current cannot be
established (read back deviation > 0.1 mA)
Operation mode is set to Current output
Overflow; Underflow; Fail-safe behaviour is activated
Operation mode is set to Frequency output
Options
The pulse output has reached maximum pulse output frequency; Fail-safe behaviour is
Operation mode is set to Pulse output
Options
The pulse output has reached maximum pulse output frequency; Fail-safe behaviour is
Operation mode is set to Pulse output
Loop current too high; Loop current too low; Fail-safe behaviour active
Operation mode is set to Current input.
This parameter is only available if
is set to Current output, Frequency
output, Pulse output or Current input.
Path
Maintenance and diagnostics → Diagnostics → Inputs and outputs → Channel 4 - in-
4.4.3.5.4 Pulse counter (read only)
Description
This parameter shows the number of pulses since startup/last reset.