EasyManua.ls Logo

EDM Solution Ultima 844 - Page 256

Default Icon
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
256
Solution Ultima 844/862/880 Installation Manual
TF008 Plug Pack (TF008)
The TF008 plug packs have been designed to be used with the EDM control panels and the PS100
Power Supply Module. The plug pack includes built in thermal fuses that under overload or fault
conditions will blow and eliminate any possible fire threat due to excessive heat build up inside the
casing.
The TF008 plug pack incorporates a three wire flying lead that enables a mains earth connection to be
made between the equipment and the plug pack. This connection may be required for lightning
protection on equipment that is connected to phone lines or for safety reasons such as earthing of
metal enclosures.
Solution Codepad Mimic Board (CC820)
The Solution Codepad Mimic Board (CC820) has been designed to allow you to have a separate
output indicator for each indicator found on the remote codepad. This will be useful to remotely
display system status information.
2 Wire Smoke Detector Interface (FA101)
The 2 Wire Smoke Detector Interface (FA101) has been designed to allow high quality 2 wire, 24 volt
DC smoke detectors to be easily connected to the Solution range of control panels. The interface
provides the 24 volts required to power the smoke detector and also provides a relay output that is
used to trigger the control panel. Multiple detectors may be connected to the same interface.
Radio Key/Keyswitch Interface (CC813)
This interface was designed to allow simple interfacing of a momentary keyswitch or radio equipment
for remote control operations to operate the control panel.
If the R/K terminal is used, a number of momentary keyswitches may be connected in parallel for
multiple arm/disarm locations. The ON and OFF terminals can be used to directly interface to any
access control system.
The HOME terminal will force the system to arm and disarm in STAY Mode 1.
There is also a PANIC terminal that allows the customer to issue a panic alarm from a remote
keyswitch or hand held radio Transmitter.
This is handy if you require your system to be radio controlled and you would like to give your
customer total control via a hand held radio remote.
ISSUE162.DOC Electronics Design and Manufacturing Pty Limited

Table of Contents