Danger: Verify power to the blade has been turned OFF and follow all local electrical safety procedures
when working with electrical circuits to prevent possible serious injury or death.
Step 2
Remove the power cables from the power terminal adapter by performing the following substeps:
Note: The SYS LED indicator on the front of the blade and PWR LED on the rear of the blade are both turned
OFF when power to the blade is shut o.
-48V
FC9549SD11 Iss.01
MAIN AMAIN B
FGGAGBG
s8102cq_1
Figure 173
Removing Power Cables
a) Detach the power feed B cable (red/white) from the terminal marked MAIN B on the power terminal adapter.
b) Detach the ground cable (black/white) for the B power feed from the terminal marked GB on the power
terminal adapter.
c) Detach the power feed A cable (red) from the terminal marked MAIN A on the power terminal adapter.
Equipment Removal