Chapter 13 Built-in Analog Function
(21) Interpolation operation value
(a) Shows the interpolation operation value of each channel.
(b) _01_DA0_INTPVAL(%UW0.1.25) : Output channel 0 interpolation operation value.
_01_DA1_INTPVAL(%UW0.1.26) : Output channel 1 interpolation operation value.
Input channel 0 operation value
%UW0.1.25
Input channel 1 operation value
%UW0.1.26
Bit15 Bit4 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
(22) Error code
(a) Shows the error code of each channel.
(b)If it is normal, the error code is 0.
(c)_01_SETTINGERR(%UW0.1.27) : Error information.
Setting error information
%UW0.1.27
Bit15 Bit4 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Type
LED sign Details
Error
10#
AD LED
Flickering 1s
intervals
Setting error of input channel range 1
#:Channel
number
(Channel0~1)
20#
Setting error of input channel filter
value
2
30#
Setting error of input channel
average value
3
40#
DA LED
Flickering 1s
intervals
Setting error of output channel
range
4
50#
Setting error of output channel
digital input value range
5
60#
Setting error of output channel
interpolation method range
6
(d) When errors of two or more are caused, the high priority error code is saved. And when the same error code is
caused in channels of two or more, the error code of low channel number is saved preferentially. In case of that
the errors are occurred at the same time in voltage output channel and current output channel, the error code of
voltage output channel is saved preferentially.