Parameter List
11
11.11 n: SPECIAL
SIEPCYEUOQ2V01A Q2V Technical Manual 379
No.
(Hex.)
Name Description
Default
(Range)
Ref.
n8-72
(0655)
Expert
Spd Obs. Method
Selection
Selects the speed estimation method. Usually it is not necessary to change this setting.
1 : Method 1
2 : Method 2
2
(1, 2)
690
n8-74
(05C3)
Expert
Light Load Iq Level
Set n8-48 [Pull-In Current (for PM Motors)] to the percentage of load current (q-axis
current) that you will apply, where E5-03 [PM Mot Rated Current (FLA)] = a setting
value of 100%.
30%
(0 - 255%)
690
n8-75
(05C4)
Expert
Mid Load Iq Level
(Low)
Set n8-78 [Mid Load Id Current] to the percentage of load current (q-axis current) that
you will apply, where E5-03 [PM Mot Rated Current (FLA)] = a setting value of 100%.
50%
(0 - 255%)
690
n8-77
(05CE)
Expert
Hvy Load Iq Level
Set n8-49 [Heavy Load Id Current] to the percentage of load current (q-axis current)
that you will apply, where E5-03 [PM Mot Rated Current (FLA)] = a setting value of
100%.
90%
(0 - 255%)
691
n8-78
(05F4)
RUN
Expert
Mid Load Id Current
Sets the level of the pull-in current as a percentage, where E5-03 [PM Mot Rated
Current (FLA)] = 100%.
0%
(0 - 255%)
691
n8-79
(05FE)
Pull-In
Curr@Deceleration
Sets the pull-in current that can flow during deceleration as a percentage of the E5-03
[PM Mot Rated Current (FLA)].
Note:
When n8-79 = 0, the drive will use the value set in n8-51 [Ac/Dec Pull-In Current].
50%
(0 - 200%)
691
n8-84
(02D3)
Expert
Polarity Det Current
Sets the current that the drive uses to estimate the initial motor magnetic pole as a
percentage where E5-03 [PM Mot Rated Current (FLA)] = 100%.
100%
(0 - 150%)
691
n8-87
(02BC)
O/P VoltLim Method
Sets the method of output voltage limit. If there is vibration in the constant output
range, set Feedforward Method. Usually it is not necessary to change this setting.
0 : Feedback Method
1 : Feedforward Method
0
(0, 1)
691
n8-88
(02BD)
VoutLimSw Level
Sets the current level at which output voltage limit sequence selection occurs as a
percentage where the motor rated current is 100%. Normally there is no need to change
this setting.
Note:
Parameter A1-02 [Control Method] selects which parameter is the motor rated
current.
• A1-02 = 5, 6 [PM OLVector, PM AOLVector]: E5-03 [PM Mot Rated Current
(FLA)]
• A1-02 = 8 [EZ Vector]: E9-06 [Motor Rated Current]
400%
(0 - 400%)
692
n8-89
(02BE)
VoutLimSwHysteresis
Sets the hysteresis width of the current level at which output voltage limit sequence
selection occurs as a percentage where the motor rated current is 100%. Normally there
is no need to change this setting.
Note:
Parameter A1-02 [Control Method] selects which parameter is the motor rated
current.
• A1-02 = 5, 6 [PM OLVector, PM AOLVector]: E5-03 [PM Mot Rated Current
(FLA)]
• A1-02 = 8 [EZ Vector]: E9-06 [Motor Rated Current]
3%
(0 - 400%)
692
n8-90
(02BF)
VoutLimSwSpeed
Sets the speed level at which output voltage limit sequence selection occurs as a
percentage where the maximum output frequency is 100%. Usually it is not necessary to
change this setting.
Note:
Parameter A1-02 [Control Method] selects which parameter is the maximum output
frequency.
• A1-02 = 5, 6 [PM OLVector, PM AOLVector]: E1-04 [Max Output Frequency]
• A1-02 = 8 [EZ Vector]: E9-02 [Maximum Speed]
200%
(0 - 200%)
692
n8-91
(02F7)
VoutLim Id Limit
Sets the limit value of feedback output voltage limit Id operation. Enabled when n8-87
= 0 [O/P VoltLim Method = Speed Feedback Form]. Usually it is not necessary to
change this setting.
-50%
(-200 - 0%)
692