Parameter Details
12
12.9 n: SPECIAL
SIEPCYEUOQ2V01A Q2V Technical Manual 689
If the motor stalls during run at constant speed, gradually increase the setting from 0.
If there is vibration or hunting, decrease the setting.
Note:
If the value is set too low, the drive will detect STPo [Motor Step-Out Detected].
If you use one motor or more than motor at low inertia and the value is too high, there can be vibration in the motor.
1 : <1:10
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is less than 1:10
There are large current ripples
2 : 1:10-1:30
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is approximately 1:10 to 1:30
Parameter n8-55 = 1 and the drive detects STPo because of an impact load or sudden acceleration/deceleration.
3 : 1:30-1:50
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is approximately 1:30 to 1:50
Parameter n8-55 = 2 and the drive detects STPo because of an impact load or sudden acceleration/deceleration.
4 : >1:50
Adjust in the following situations.
The ratio between the motor inertia and machine inertia is more than 1:50
Parameter n8-55 = 3 and the drive detects STPo because of an impact load or sudden acceleration/deceleration.
n8-57: High-Freq Injection
No.
(Hex.)
Name Description
Default
(Range)
n8-57
(0574)
High-Freq Injection
Sets the function that detects motor speed with high frequency injection.
0
(0, 1)
Note:
When you set n8-57 = 1, doHigh Frequency Injection Auto-Tuning.
When there is high frequency injection, the motor will make an excitation sound.
When you use Zero Speed Control, set E1-09 [Min Output Frequency] = 0.0.
0 : Disabled
Use this setting with SPM motors. The speed control range is approximately 1:20.
When n8-57 = 0, you cannot set E1-09 [Min Output Frequency] 1/20 of the value of E1-06 [Base Frequency].
1 : Enabled
The speed control range changes to 1:100 to give sufficient speed detection at low speeds.
Note:
It is not available with an SPM motor.
n8-62: Output Volt Limit Level
No.
(Hex.)
Name Description
Default
(Range)
n8-62
(057D)
Expert
Output Volt Limit Level
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not necessary
to change this parameter.
200 V Class: 200.0 V, 400
V: 400.0 V
(200 V Class: 0.0 to 230.0
V, 400 V Class: 0.0 to 460.0
V)
Set this parameter lower than the input power supply voltage.