EasyManuals Logo

Omron Q2V Series User Manual

Omron Q2V Series
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #708 background imageLoading...
Page #708 background image
12.10 o: KEYPAD
708 SIEPCYEUOQ2V01A Q2V Technical Manual
o4-11: Flt.History Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-11
(0510)
Flt.History Initialization
Resets the records of Monitors U2: FAULT and U3: FAULT HISTORY.
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Init Parameters], the drive will not reset the records for U2-xx and U3-xx.
0 : No Reset
Keeps the records of Monitors U2-xx and U3-xx.
1 : Reset
Resets the records for Monitors U2-xx and U3-xx. After the reset, the drive automatically resets o4-11 to 0.
o4-12: kWh Monitor Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for U4-10 [kWh Lower 4Digits] and U4-11 [kWh Upper 5Digits].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Init Parameters], the drive will not reset U4-10 and U4-11.
0 : No Reset
Keeps the monitor values for U4-10 and U4-11.
1 : Reset
Resets the values of U4-10 and U4-11. After the reset, the drive automatically resets o4-12 to 0.
o4-13: NumOfRunCom Init Counter
No.
(Hex.)
Name Description
Default
(Range)
o4-13
(0528)
NumOfRunCom Init
Counter
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [No of Travels(L)], and
U4-25 [No of Travels(H)].
0
(0, 1)
0 : No Reset
Keeps the monitor values for U4-02, U4-24, and U4-25.
1 : Reset
Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.
o4-22: Time Format
No.
(Hex.)
Name Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD keypad.
0
(0 - 2)
Sets the display of the time shown in the upper-left of the LCD keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
o4-23: Date Format
No.
(Hex.)
Name Description
Default
(Range)
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LCD keypad.
0
(0 - 2)
Sets the date format that the drive uses for the fault history and other records.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2V Series and is the answer not in the manual?

Omron Q2V Series Specifications

General IconGeneral
BrandOmron
ModelQ2V Series
CategoryInverter
LanguageEnglish

Related product manuals