EasyManuals Logo

Omron RX2 Series User Manual

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #289 background imageLoading...
Page #289 background image
6 - 51
6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-6 Thermal Protection of Motor (Electronic Thermal)
6
6-6-1 Electronic Thermal Setting
Constant Torque Characteristics [bC111]=01
Use this setting to use the constant-torque motor
(Ex.3) For induction motor rated current: 64A, [bC110]=64(A)
Base frequency [Hb104]=50 Hz, output frequency =5 Hz
When the first electronic thermal level [bC110] is 64 A, the reduction ratio is ×1.0 for operations at a
base frequency of 50 Hz and output frequency of 5 Hz and the electronic thermal time-limited char-
acteristics are given in the lower part of Example 3.
Since Example 1 shows the case of the reduction ratio ×1, a trip occurs in 60 seconds when an elec-
tric current of 150% ×1 of the motor rated current flows continuously. The performance in the exam-
ple 3 is the same as the one in the example 1.
Free Settings [bC111]=02
To protect the motor, the electronic thermal characteristics can be freely set in accordance with the
load.
X1.0
0
50
0
60
Inverter
Output frequency (Hz)
Base frequency
Reduction ratio
70.4
(110%)
96
(150%)
128
(200%)
60
3
0
×1
Trip time (s)
Motor current (A)
(Ratio to motor rated current)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron RX2 Series and is the answer not in the manual?

Omron RX2 Series Specifications

General IconGeneral
BrandOmron
ModelRX2 Series
CategoryInverter
LanguageEnglish

Related product manuals