EasyManua.ls Logo

Omron RX2 Series - Page 324

Omron RX2 Series
920 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Advanced Settings
7 - 16
High-function General-purpose Inverter RX2 Series User’s Manual
Parameter
Item Parameter Data Description
Default
data
Control mode
selection,
1st-motor
[AA121] 08 To use the sensorless vector control (IM). 00
Speed response
for Async.M,
1st-motor
[HA115] 0 to 1000(%)
To adjust the responsiveness of the control.
A larger value enhances the responsiveness.
100
Boost value at start
for
Async.M-SLV/IM-C
LV, 1st-motor
[HC111] 0 to 50(%)
To adjust the current command at the start when
the starting torque is not sufficient.
0
Secondary resis-
tance correction,
1st-motor
[HC113]
00 Disabled
00
01 Enabled Requiring a temperature thermistor.
Counter direction
run protection
selection,
1st-motor
[HC114]
00 Disabled
00
01
Enabled Limit the output to prevent the output in
the reverse direction.
Torque current ref-
erence filter time
constant, 1st-motor
[HC120] 0 to 100(ms) To adjust the filter for the torque current. 2
Speed feedfor-
ward compensa-
tion gain, 1st-motor
[HC121] 0 to 1000(%)
To adjust the feed forward control of the speed
controller.
0
Phenomenon Estimated cause(s) Exemplar measures to be taken
Socks occur during the
revolutions at the start.
The control system
has a speed response
that is too high.
Make an adjustment by decrementing the response adjust-
ment [HA115] by 5% each time.
Make an adjustment by decrementing the IM motor constant
J [Hb118] by 5% each time.
Make an adjustment by decrementing the boost amount at
the start [HC111] by 5% each time.
Unsteady revolutions
at low speeds, result-
ing in fluctuating revo-
lutions.
The control system
has a speed response
that is too low.
Make an adjustment by incrementing the response adjust-
ment [HA115] by 5% each time.
Make an adjustment by incrementing the IM motor constant
J [Hb118] by 5% each time.
The motor is hunting.
The control system
has a speed response
that is too low.
Make an adjustment by decrementing the response adjust-
ment [HA115] by 5% each time.
Make an adjustment by decrementing the IM motor constant
J [Hb118] by 5% each time.
When a load in the
motor-stopping direc-
tion is applied to the
motor, the revolution
frequency becomes
lower.
The motor constant R2
is set at too small a
value.
Make an adjustment by incrementing the IM motor constant
R2 [Hb112] by 5% of the current value each time.
When a load in the
motor-stopping direc-
tion is applied to the
motor, the revolution
frequency becomes
higher.
The motor constant R2
is set at too large a
value.
Make an adjustment by decrementing the IM motor constant
R2 [Hb112] by 5% of the current value each time.
When a load in the
motor-stopping direc-
tion is applied to the
motor, the revolution
frequency becomes
higher.
Insufficient regenera-
tive torque at low
speeds.
Make an adjustment by incrementing the IM motor constant
R1 [Hb110] by 5% of the current value each time.
Make an adjustment by incrementing the IM motor constant
I0 [Hb116] by 5% of the current value each time.

Table of Contents

Related product manuals