7 Advanced Settings
7 - 68
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.) Frequency matching operation after free-run stop [FRS]
(Ex.) Frequency matching operation after reset [RS]
Note If the frequency matching after reset has been set, starting after power-on will also occur with frequency
matching.
Item Parameter Data Description
Default
data
Selection of restart
mode @over-volt-
age
[bb-30] 01 Performs frequency matching restart. 01
Wait time of restart
@over-voltage
[bb-31] 0.3 to 100.0(s)
Sets the wait time after the retry operation on
overvoltage.
0.3
Frequency Matching after Free-run Stop [FRS] Release [bb-40]=01
Item Parameter Data Description
Default
data
Restart mode after
FRS release
[bb-40] 01 Performs frequency matching restart. 00
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s)
Sets the wait time after the free-run stop
release.
0.3
Frequency Matching After Reset [RS] [bb-41]=01
Item Parameter Data Description
Default
data
Restart mode after
RS release
[bb-41] 01 Performs frequency matching restart. 00
Retry wait time
before motor
restart
[bb-26] 0.3 to 100.0(s) Sets the wait time after the reset release. 0.3
0
[bb-26]
[bb-42]
Free-running
Restarting with frequency matching
Operation
command FW
Free-running
stop FRS
Motor speed
0
[bb-26]
[bb-42]
Free-running
Restarting with frequency matching
Operation
command FW
Reset RS
Motor speed

Table of Contents