8 Applied Settings
8 - 128
High-function General-purpose Inverter RX2 Series User’s Manual
When [CE105] = 00
When [CE105] = 01
Parameter
Item Parameter Data Description
Default
data
Output terminal func-
tion selection 11-15
[CC-01] to
[CC-05]
035
036
035 [OL]: Overload prewarning signal 1 is
output.
036 [OL2]: Overload prewarning signal 2 is
output.
OFF: Less than or equal to the overload pre-
warning signal level
ON: More than or equal to the overload pre-
warning signal level
-
Relay output terminal
function selection
16A-16C
[CC-06] -
Relay output terminal
function selection
AL1-AL0/AL2-AL0
[CC-07] -
Over current signal
output mode selection,
1st motor
[CE105]
00 Valid in operation
01
01 Valid only in constant speed operation
Over current detection
level 1, 1st motor
[CE106]
(0.0 to 2.0) x
inverter rated
current
*1
Specify the current level at which the over-
load prewarning signal is output.
The signal will be output when the current
exceeds the overload prewarning signal
level.
1.0×
Inverter
rated
current
[FM] monitor bias
adjustment
[CE107]
1.0×
Inverter
rated
current
[CE106]
[CE107]
Overload prewarning level
Output current
Output
frequency
Output signal
[OL]
Output signal
[OL2]
[CE106]
[CE107]
Output current
Output
frequency
Output signal
[OL]
Output signal
[OL2]
Overload prewarning level