8 Applied Settings
8 - 160
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.1) Cancelling the trip at ON ([CA-72]=00,02)
(Ex.2) Cancelling the trip at OFF ([CA-72]=01,03)
(Ex.3) Validating resetting at normal ([CA-72]=00,01)
Constant (voltage) for
frequency acquisition
restarting
[bb-45]
0.10 to 30.00
(sec)
The start time of frequency acquisition 0.5
Excessive current pre-
vention level at the
time of frequency
acquisition
[bb-46]
(0.2 to 2.0) ×
Inverter rated
current
*1
The limit current value setting for the exces-
sive current prevention level at the time of
frequency acquisition
1.0×
Inverter
rated
current
Start frequency
selection at the time of
frequency acquisition
[bb-47]
00 Frequency at the time of interruption
0001 Maximum frequency
02 Set frequency
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting
path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00
(A,V). When the data of [CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
Examples of Resetting Operations
Item Parameter Data Description
Default
data
Restarts in accordance with [bb-41]
Output
frequency
Operation
instruction
RS input