9 Communications Functions
9 - 22
High-function General-purpose Inverter RX2 Series User’s Manual
000Fh 000Eh Input terminal B R/W
1: ON
0: OFF
*1
0010h 000Fh (Reserved)
0011h 0010h (Reserved)
0012h 0011h (Reserved)
0013h 0012h (Reserved)
0014h 0013h (Reserved)
0015h 0014h Operating status R
1: Rotating in normal direction, rotating in
reverse direction
0: Other than rotating in normal/reverse
rotation (linked with dA-03)
0016h 0015h Rotation direction R
1: Rotating in reverse direction
0: Rotating in normal direction (linked with
dA-03)
0017h 0016h
Inverter operation ready
completion
R
1: Ready
0: Not ready
0018h 0017h (Reserved)
0019h 0018h Output terminal 11 R
1: ON
0: OFF
001Ah 0019h Output terminal 12 R
1: ON
0: OFF
001Bh 001Ah Output terminal 13 R
1: ON
0: OFF
001Ch 001Bh Output terminal 14 R
1: ON
0: OFF
001Dh 001Ch Output terminal 15 R
1: ON
0: OFF
001Eh 001Dh Output terminal 16 R
1: ON
0: OFF
001Fh 001Eh Output terminal AL R
1: ON
0: OFF
0020h to 0048h 001Fh to 0047h (Reserved)
0049h 0048h Data being written R
1: Being written
0: Normal state
004Ah 0049h CRC error R
1: With error
0: No error
*2
004Bh 004Ah Overrun error R
1: With error
0: No error
*2
004Ch 004Bh Framing error R
1: With error
0: No error
*2
004Dh 004Ch Parity error R
1: With error
0: No error
*2
004Eh 004Dh Sum check error R
1: With error
0: No error
*2
004Fh 004Eh (Reserved)
*1. While either the control circuit terminal block or the coil is ON, an inverter becomes ON. The input of the control circuit
terminal block is prioritized. In some cases, the coil ON status cannot be reset from the master due to communication
disconnection. To turn the coil OFF, change the control circuit terminal block from ON to OFF.
*2. Communication errors are kept until an error reset is input. The reset can be available during the operation.
Coil No.
Modbus coil
spec. No.
Item R/W Description