9 Communications Functions
9 - 56
High-function General-purpose Inverter RX2 Series User’s Manual
31CFh 31CEh
Input source selection of Pro-
cess data 1 for PID1
AH-51 R/W
00: Disabled
01: Ai1 terminal input
02: Ai2 terminal input
03: Ai3 terminal input
04: (Reserved)
05: (Reserved)
06: (Reserved)
08: RS 485
09: Option 1
10: Option 2
11: Option 3
12: Pulse string input: Inverter
13: Pulse string input: Option
-
31D0h 31CFh
Input source selection of Pro-
cess data 2 for PID1
AH-52 R/W
00: Disabled
01: Ai1 terminal input
02: Ai2 terminal input
03: Ai3 terminal input
04: (Reserved)
05: (Reserved)
06: (Reserved)
08: RS 485
09: Option 1
10: Option 2
11: Option 3
12: Pulse string input: Inverter
13: Pulse string input: Option
-
31D1h 31D0h
Input source selection of Pro-
cess data 3 for PID1
AH-53 R/W
00: Disabled
01: Ai1 terminal input
02: Ai2 terminal input
03: Ai3 terminal input
04: (Reserved)
05: (Reserved)
06: (Reserved)
08: RS 485
09: Option 1
10: Option 2
11: Option 3
12: Pulse string input: Inverter
13: Pulse string input: Option
-
31D2h 31D1h
Calculation symbol selection
of Process data for PID1
AH-54 R/W
01: Addition
02: Subtraction
03: Multiplication
04: Division
05: Square root of FB1
06: Square root of FB2
07: Square root of (FB1-FB2
08: Average of PV-1 to PV-3
09: Minimum data of PV-1 to
PV-3
10: Maximum data of PV-1 to
PV-3
-
31D8h 31D7h
PID1 gain change method
selection
AH-60 R/W
00: Only gain 1
01: [PRO] terminal switch
-
31D9h 31D8h PID1 proportional gain 1 AH-61 R/W 0 to 1000 0.1
31Dah 31D9h PID1 integral time constant 1 AH-62 R/W 0 to 36000 0.1(s)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution