9 Communications Functions
9 - 90
High-function General-purpose Inverter RX2 Series User’s Manual
4282h 4281h
Output voltage monitor
optional output enable
PA-26 R/W
00: Disabled
01: Enabled: parameter setting
[PA-27]
02: (Enabled: set from [Ai1]
03: Enabled: set from [Ai2]
04: (Enabled: set from [Ai3]
05: (Reserved)
06: (Reserved)
07: (Reserved)
-
4283h 4282h
Output voltage monitor
optional output value setting
PA-27 R/W
200V class: 0-3000
400V class: 0-6000
0.1(V)
4284h 4283h
Output torque monitor
optional output enable
PA-28 R/W
00: Disabled
01: Enabled: parameter setting
[PA-29]
02: (Enabled: set from [Ai1]
03: Enabled: set from [Ai2]
04: (Enabled: set from [Ai3]
05: (Reserved)
06: (Reserved)
07: (Reserved)
-
4285h 4284h
Output torque monitor
optional output value setting
PA-29 R/W -5000 to 5000 0.1(%)
4286h 4285h
Start with frequency matching
optional Setting enable
PA-30 R/W
00: Disabled
01: Enabled: parameter setting
[PA-31]
02: Enabled: set from [Ai1]
03: Enabled: set from [Ai2]
04: Enabled: set from [Ai3]
05: (Reserved)
06: (Reserved)
07: (Reserved)
-
4287h 4286h
Start with frequency matching
optional value setting
PA-31 R/W 0 to 59000 0.01(Hz)
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A,V). When
the data of [CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution