11 - 27
11 Options
High-function General-purpose Inverter RX2 Series User’s Manual
11-5 DC Reactor (Model: 3G3AX-DL)
11
11-5-2 External Dimensions
3-phase
400 VAC
3G3AX-
DL4110
Fig. 2
11 146 120 250 – 105 124 96 7 × 11 M5 5.2
5.5 mm
2
min.
3G3AX-
DL4150
15 146 120 252 – 120 124 96 7 × 11 M6 7.0
14 mm
2
min.
3G3AX-
DL4220
Fig. 3
18.5, 22 120 175 352 140 145 98 151 7 × 11 M6 9.5
22 mm
2
min.
3G3AX-
DL4300
30 120 175 356 140 145 98 151 7 × 11 M8 9.5
30 mm
2
min.
3G3AX-
DL4370
37 120 175 386 155 150 98 151 7 × 11 M8 13.5
38 mm
2
min.
3G3AX-
DL4450
45 160 190 416 180 145 120 168 7 × 11 M8 16.5
60 mm
2
min.
3G3AX-
DL4550
55 160 190 416 190 170 120 168 7 × 11 M8 23.0
38 mm
2
x 2 min.
Inverter
input
power
supply
Model
Fig.
No.
Applica-
ble motor
capacity
[kW]
Dimensions [mm]
Weight
[kg]
Standard appli-
cable wire
W D H A B