Under the System tab, you can set Notifications for Minor and Major Alarms/Clearances.
The temperature readouts used for the Alarms are generated by the CPU temperature
sensor.
Also, you can set the temperature threshold value for Minor/Major alarms, and define a
retry value by determining how many readings (1/min.) the temperature must exceed the
threshold value before an alarm/clearance is triggered.
The default temperature threshold value for both Minor, and Major Alarms is 100°C. With
simultaneous alarm triggerings, the Major Alarm will override the Minor Alarm, i.e. you will
be notified only about the Major Alarm. If you want to be notified early about a rise in tem-
perature, a recommended setting for the Minor Alarm temperature would be 90°C. Please