Parameters
List of Parameters
1-116
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines fixed frequency setpoint 5.
Note: See parameter P1001 (fixed frequency 1).
Description: Defines fixed frequency setpoint 6.
Note: See parameter P1001 (fixed frequency 1).
Description: Defines fixed frequency setpoint 7.
Note: See parameter P1001 (fixed frequency 1).
Description: Defines fixed frequency setpoint 8.
Note: See parameter P1001 (fixed frequency 1).
Description: Defines fixed frequency setpoint 9.
Note: See parameter P1001 (fixed frequency 1).
p1005[0...2] Fixed frequency 5 / Fixed frequency 5
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 20.00 [Hz]
p1006[0...2] Fixed frequency 6 / Fixed frequency 6
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 25.00 [Hz]
p1007[0...2] Fixed frequency 7 / Fixed frequency 7
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 30.00 [Hz]
p1008[0...2] Fixed frequency 8 / Fixed frequency 8
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 35.00 [Hz]
p1009[0...2] Fixed frequency 9 / Fixed frequency 9
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 40.00 [Hz]