EasyManua.ls Logo

Siemens CU240S DP-F - F00027 Overcurrent on W phase; F00028 Power limit exceeded during regeneration; F00029 EM brake overcurrent; F00035 Auto restart after n

Siemens CU240S DP-F
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of Fault and Alarm messages
3-382
ยฉ Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
F00027 Overcurrent on W phase
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: This hardware fault caused by the following events:
โ€ข Over current trip on W phase
โ€ข Earth Fault
Remedy: Check Inverter and Motor wiring
F00028 Power limit exceeded during regeneration
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Occurs if motor is driven by an active load, causing motor to go into excessive regeneration.
Occurs at very high load inertias, when ramping down.
Remedy: โ€ข Reduce regeneration from active load
โ€ข Reduce ramp down rate
โ€ข Increase Imax regeneration limit in p1253
F00029 EM brake overcurrent
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: โ€ข
Remedy:
F00035 Auto restart after n
Reaction: OFF 2 (OFF 3)
Acknowledge: Power on
Cause: Auto restart attempts exceed value of p1211.
Remedy:

Table of Contents

Other manuals for Siemens CU240S DP-F

Related product manuals