Parameters
List of Parameters
1-292
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Contains the current safety password. For safety commissioning or safety reset the value of r9760 has to be
entered into p9761.
If the password in p9761 is not set correctly to the value in r9760, none of the safety parameters can be written and
a fault F1659 is generated.
This parameter is changed automatically to the password in p9763 when the new value of p9762 is identical to the
confirmation password in p9763.
Description: The safety password of r9760 is entered in this parameter to get access to changing the safety parameters.
If p9761 is not identical to r9760 a fault F1659 is generated.
Note: The default value of this parameter is 0. This indicates that no password has been set.
The range of the password values are 1000 to 99999.
Description: Parameter to change the safety password. The new safety password is entered in p9762 and then confirmed by
entering same value in p9763.
Note: The default value of this parameter is 0. This indicates that no password has been set.
The range of the password values are 1000 to 99999.
The values in p9762 and p9763 are set to zero automatically when the new password is accepted.
Description: Confirm a safety password change. Parameter needs to be set to the same value as p9762. Only then then pass-
word change of p9762 is stored in r9760 as new password. If p9763 is not identical to p9762, both values are
cleared and r9760 is not updated.
Note: The default value of this parameter is 0. This indicates that no password has been set.
The range of the password values are 1000 to 99999.
The values in p9762 and p9763 are set to zero automatically when the new password is accepted.
r9760 SI internal password / SI intern password
CU240S DP-F Access level: 3 P-Group: Safety Integrated Data type: Unsigned32
Unit: - Data set: -
p9761 SI input password / SI input password
CU240S DP-F Access level: 3 P-Group: Safety Integrated Data type: Unsigned32
Quick comm. NO Active: NO Data set: -
Can be changed: -
Min Max Factory setting
1000 99999 1000
p9762 SI change password / SI change password
CU240S DP-F Access level: 3 P-Group: Safety Integrated Data type: Unsigned32
Quick comm. NO Active: NO Data set: -
Can be changed: -
Min Max Factory setting
1000 99999 1000
p9763 SI change password confirmation / SI passwd. confirm
CU240S DP-F Access level: 3 P-Group: Safety Integrated Data type: Unsigned32
Quick comm. NO Active: NO Data set: -
Can be changed: -
Min Max Factory setting
1000 99999 1000

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals