Faults and Alarms
List of Fault and Alarm messages
3-386
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
F00055 BOP-EEPROM Fault
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Read or write failure while saving non-volatile parameter to EEPROM on BOP whilst parameter cloning.
Remedy: • Factory Reset and new parameterization
• Change BOP
• r0949 = 5096 : Use a BOP with a bigger EEPROM
• r0949 = 9160 : Use a BOP with a smaller EEPROM
Note: • r0949 = 1000 + Block No: Reading data block failed
• r0949 = 3000 + Block No: Reading data block CRC failed
• r0949 = 4000 + Block No: Writing data block failed
• r0949 = 5096 : BOP EEPROM too Small
• r0949 = 6000 + Block No: writing data block verify failed
• r0949 = 7000 + Block No: Reading data block at wrong time
• r0949 = 8000 + Block No: writing data block at wrong time
• r0949 = 9160 : Drive EEPROM too Small
F00056 BOP not fitted
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Trying to initiate parameter cloning without BOP fitted.
Remedy: Fit BOP and try again.
F00057 BOP fault
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: • Parameter cloning with empty BOP.
• Parameter cloning with invalid BOP.
Remedy: Download to BOP or replace BOP.
F00058 BOP contents incompatible
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Trying to initiate parameter cloning with BOP created on another type of drive.
Remedy: Download to BOP from this type of drive.
F00060 Asic Timeout
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Internal communications failure
• r0949 = 0: HW reported Link Fail
• r0949 = 1: SW reported Link Fail
Remedy: Check connection between inverter power module and inverter control unit
Fault appears sporadically:
• Communication failure due to EMC problems
• Check - and if necessary - improve EMC
• Use EMC filter
Fault appears immediately when mains voltage is applied and an ON command is given.
• If fault persists, change inverter.
• Contact Service Department.

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals