List of Parameters
Parameters
1-149
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Enters differential time constant for Vdc controller.
Description: Limits maximum effect of Vdc max controller.
Description: Enables/disables auto-detection of switch-on levels for Vdc max controller.
Values: 0: Disabled
1: Enabled
Description: Enters reaction for kinetic buffering controller (Vdc-min controller).
Depending on the setting selected, the frequency limit defined in P1257 is used to either hold the speed or disable
pulses.
If not enough regeneration is produced, drive may trip with undervoltage.
Values: 0: Maintain DC-link until trip
1: Maintain DC-link until trip / stop
2: Control stop
Note: P1256 = 0:
Maintain DC-link voltage until mains is returned or drive is tripped with undervoltage.
The frequency is kept above the frequency limit provided in P1257.
P1256 = 1:
Maintain DC-link voltage until mains is returned or drive is tripped with undervoltage or pulses are disabled when
frequency falls below the limit in P1257.
P1256 = 2:
This option ramps down the frequency to standstill even when mains return.
If mains does not return, frequency brought down under the control of vdc-min controller until P1257 limit. Then
pulses are disabled or undervoltage has occurred.
If mains return, then an OFF1 is active until P1257 limit. Then pulses are disabled.
p1252[0...2] Differential time Vdc-controller / Diff.time Vdc ctrl
PM240 Access level: 4 P-Group: - Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: C, U, T
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 1.0 [ms]
p1253[0...2] Vdc-controller output limitation / Vdc ctrl outp. lim
Access level: 3 P-Group: - Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: C, U, T
Min Max Factory setting
0.00 [Hz] 600.00 [Hz] 10.00 [Hz]
p1254 Auto detect Vdc switch-on levels / Autodet Vdc ON lev
PM240 Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: YES Data set: -
Can be changed: C, T
Min Max Factory setting
0 1 1
p1256[0...2] Reaction of kinetic buffering / Reaction of KIB
PM240 Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: C, T
Min Max Factory setting
0 2 0

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals