Page #62 background image
Parameters
List of Parameters
1-62
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Ambient temperature of motor at time of motor data identification.
It is only allowed to change the value when the motor is cold.
A motor identification has to be made after changing the value.
Description: Overtemperature of stator iron.
Note: Temperature rises are valid for sinusoidal operations (line supply temperature rises).
Temperature rises due to converter operation (modulation losses) and output filter are also considered.
Description: Overtemperature of the stator winding.
It is only allowed to change the value when the motor is cold.
A motor identification has to be made after changing the value.
Note: Temperature rises are valid for sinusoidal operations (line supply temperature rises).
Temperature rises due to converter operation (modulation losses) and output filter are also considered.
Description: Overtemperature of the rotor winding.
Note: Temperature rises are valid for sinusoidal operations (line supply temperature rises).
Temperature rises due to converter operation (modulation losses) and output filter are also considered.
Description: Displays ambient temperature of motor mass model.
p0625[0...2] Ambient motor temperature / Ambient mot. temp.
Access level: 3 P-Group: Motor Data type: Floating Point
Quick comm. YES Active: YES Data set: DDS
Can be changed: C, U, T
Min Max Factory setting
-40.0 [°C] 80.0 [°C] 20.0 [°C]
p0626[0...2] Overtemperature stator iron / Overtemp.stat.iron
Access level: 4 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [°C] 200.0 [°C] 50.0 [°C]
p0627[0...2] Overtemperature stator winding / Overtemp.stat.wind
Access level: 4 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [°C] 200.0 [°C] 80.0 [°C]
p0628[0...2] Overtemperature rotor winding / Overtemp.rot. wind
Access level: 4 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [°C] 200.0 [°C] 100.0 [°C]
r0630[0...2] CO: Motor model ambient temperature / Mot. model amb. te
Access level: 4 P-Group: Motor Data type: Floating Point
Unit: [°C] Data set: DDS

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals