List of Parameters
Parameters
1-123
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets the signal source for the setting command to accept the setting value for the motorized potentiometer. The
value becomes effective for a 0/1 edge of the setting command.
Notice: Refer to: P1044
Description: Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0/1 edge of the setting
command.
Notice: Refer to: P1043
Description: Displays the motorized potentiometer setpoint before it passed the MOP RFG.
Description: Sets the ramp-up time for the internal MOP ramp-function generator.
The setpoint is changed from zero up to limit defined in P1082 within this time.
Notice: Refer to: P1048, P1082
Description: Sets the ramp-down time for the internal MOP ramp-function generator.
The setpoint is changed from limit defined in P1082 down to zero within this time.
Notice: Refer to: P1047, P1082
Description: Displays output frequency of motor potentiometer setpoint ([Hz]).
p1043[0...2] BI: MOP accept rampgenerator setpoint / MOP acc RFG setpo
Access level: 3 P-Group: Setpoints Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 0
p1044[0...2] CI: MOP rampgenerator setpoint / MOP RFG setpoint
Access level: 3 P-Group: Setpoints Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 0
r1045 CO: MOP input frequency of the RFG / MOP RFG input
Access level: 3 P-Group: Setpoints Data type: Floating Point
Unit: [Hz] Data set: -
p1047[0...2] MOP ramp-up time of the RFG / MOP ramp-up time
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: NO Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [s] 1000.00 [s] 10.00 [s]
p1048[0...2] MOP ramp-down time of the RFG / MOP rampdown time
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: NO Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [s] 1000.00 [s] 10.00 [s]
r1050 CO: Act. Output freq. of the MOP / MOP outp.freq.
Access level: 2 P-Group: Setpoints Data type: Floating Point
Unit: [Hz] Data set: -