Parameters
List of Parameters
1-218
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be viewed.
Index: [0] = Recent Warnings --, warning 1
[1] = Recent Warnings --, warning 2
[2] = Recent Warnings -1, warning 3
[3] = Recent Warnings -1, warning 4
Notice: Indices 0 and 1 are not stored.
Note: The LED indicates the warning status in this case.
The keypad will flash while a warning is active.
Description: Displays number of warning (up to 4) since last reset.
Set to 0 to reset the warning history.
Description: Displays run time counter.
It is the total time the drive has been powered up. When power is switched off, the value is saved, then restored on
powerup.
The run time counter will be calculate as followed:
Multiply the value in r2114[0], by 65536 and then add it to the value in r2114[1]. The resultant answer will be in sec-
onds.
This means that r2114[0] is not days.
Total powerup time = 65536 * r2114[0] + r2114[1] seconds.
Example: If r2114[0] = 1 and r2114[1] = 20864
We get 1 * 65536 + 20864 = 86400 seconds which equals 1 day.
Index: [0] = System Time, Seconds, Upper Word
[1] = System Time, Seconds, Lower Word
Note: When the real time is not given in P2115, the time in this parameter is used by r0948 to indicate when a fault has
occured.
See r0948 (fault time).
r2110[0...3] CO: Warning number / Warning number
Access level: 2 P-Group: Messages Data type: Unsigned16
Unit: - Data set: -
p2111 Total number of warnings / Total no. warnings
Access level: 3 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: T
Min Max Factory setting
0 4 0
r2114[0...1] Run time counter / Run time counter
Access level: 3 P-Group: Messages Data type: Unsigned16
Unit: - Data set: -