Parameters
List of Parameters
1-208
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays control word 1 from USS on RS232 (word 1 within USS).
Description: Displays control word 2 from USS on RS232 (i.e. word 4 within USS).
Dependency: P0700 = 4 (USS on RS232) and P0719 = 0 (Cmd / Setpoint = BICO parameter).
Description: Displays control word 2 from USS on RS232 (i.e. word 4 within USS).
Dependency: P0700 = 4 (USS on RS232) and P0719 = 0 (Cmd / Setpoint = BICO parameter).
r2032.0...15 BO: CtrlWrd1 from USS on RS232 / CtrlWd1 <- USS
Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OFF2: Electrical stop No Yes -
02 OFF3: Fast stop No Yes -
03 Pulse enable Yes No -
04 RFG enable Yes No -
05 RFG start Yes No -
06 Setpoint enable Yes No -
07 Fault acknowledge Yes No -
08 JOG right Yes No -
09 JOG left Yes No -
10 Control from PLC Yes No -
11 Reverse (setpoint inversion) Yes No -
13 Motor potentiometer MOP up Yes No -
14 Motor potentiometer MOP down Yes No -
15 CDS Bit 0 (Hand/Auto) Yes No -
r2033.0...15 BO: CtrlWrd2 from USS on RS232 / CtrlWd2 <- USS
PM240 Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed frequency Bit 0 Yes No -
01 Fixed frequency Bit 1 Yes No -
02 Fixed frequency Bit 2 Yes No -
03 Fixed frequency Bit 3 Yes No -
04 Drive Dataset (DDS) Bit 0 Yes No -
05 Drive Dataset (DDS) Bit 1 Yes No -
08 Enable PID Yes No -
09 Enable DC brake Yes No -
11 Enable Droop Yes No -
12 Torque control Yes No -
13 External fault 1 No Yes -
15 Command Dataset (CDS) Bit 1 Yes No -
r2033.0...15 BO: CtrlWrd2 from USS on RS232 / CtrlWd2 <- USS
PM250
PM260
Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed frequency Bit 0 Yes No -
01 Fixed frequency Bit 1 Yes No -
02 Fixed frequency Bit 2 Yes No -
03 Fixed frequency Bit 3 Yes No -
04 Drive Dataset (DDS) Bit 0 Yes No -
05 Drive Dataset (DDS) Bit 1 Yes No -
08 Enable PID Yes No -
11 Enable Droop Yes No -
12 Torque control Yes No -
13 External fault 1 No Yes -
15 Command Dataset (CDS) Bit 1 Yes No -

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals