Description: Defines fixed value for the max. permissible motoring active power (motoring power limitation).
Parameter P1530 limits the torque in addition to the act. frequency as displayed in the following characteristic.
Description: Enters fixed value for the max. permissible regenerative active power (regenerative power limitation).
Note: See parameter P1530.
Description: Displays maximum torque motoring current component.
p1530[0...2] Motoring power limitation / Motoring power lim
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 8000.0 0.75
p1530
def
p1530
max
0307P3 â‹…=
0307P5.2 â‹…=
M
f
f 2
P
M
⋅π⋅
=
Power limitation (motoring, regenerative)
p1530
p1531
p1530
p1531
p1531[0...2] Regenerative power limitation / Regener. power lim
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-8000.0 0.0 -0.75
p1531
min
P0307 1- â‹…=
p1531
def
P0307 1- â‹…=
r1536 CO: Max. trq. motoring current / Max trq mot cur
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -