EasyManuals Logo

Siemens CU240S DP-F Parameter Manual

Siemens CU240S DP-F
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
Parameters
List of Parameters
1-14
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications.
Values: 0: User defined parameter list - see P0013 for details on use
1: Standard: Allows access into most frequently used parameters.
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only.
4: Service: Only for use by authorized service, password protected
Note: Only valid for control units with OP.
Description: Filters parameters according to functionality to enable a more focussed approach to commissioning.
Values: 0: All parameters
2: Inverter
3: Motor
4: Speed sensor
5: Technol. application / units
7: Commands, binary I/O
8: AI and AO
10: Setpoint channel / RFG
12: Drive features
13: Motor control
19: Motor identification
20: Communication
21: Alarms / warnings / monitoring
22: Technology controller
p0003 User access level / User access level
Access level: 1 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
0 4 1
p0004 Parameter filter / Parameter filter
CU240E
CU240S
CU240S DP
CU240S PN
Access level: 1 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
0 22 0

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals