Parameters
List of Parameters
1-176
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays maximum torque of the regenerative current component.
Description: Displays total upper torque limitation.
Description: Displays total lower torque limitation.
Description: Defines fixed value of flux setpoint in [%] relative to rated motor flux.
Note: If P1570 > 100 %, the flux setpoint rises according to the load from 100 % to the value of P1570 between idling and
nominal load.
Description: Sets dynamic voltage headroom for vector control.
Description: Sets the efficiency optimization for closed-loop vector control in [%]. When optimizing the efficiency, the flux set-
point is adapted as a function of the load.
Note: If P1580 > 0, the dynamics for speed control (P1470, P1472) are restricted to prevent vibration.
When no load is applied, a value of 100 % produces full flux reduction (i.e. to 50 % of rated motor flux).
When using optimization, it is necessary to increase the smoothing time of the flux setpoint (P1582).
r1537 CO: Max trq regenerative current / Max trq reg cur
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r1538 CO: Upper torque limit (total) / Total up TrqLim
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Unit: [Nm] Data set: -
r1539 CO: Lower torque limit (total) / Total lw TrqLim
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Unit: [Nm] Data set: -
p1570[0...2] CO: Fixed value flux setpoint / Fval flux setp
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
50.0 [%] 200.0 [%] 100.0 [%]
p1574[0...2] Dynamic voltage headroom / Dyn. volt headroom
Access level: 3 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [V] 150 [V] 10 [V]
p1580[0...2] Efficiency optimization / Efficiency optimiz
Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [%] 100 [%] 0 [%]