Description: Nominal motor power [kW/hp] from rating plate - see P0304.
Dependency: If P0100 = 1, values will be in [hp] - see P0304 (rating plate).
Changeable only when P0010 = 1 (quick commissioning).
Note: Default value is depending on inverter type and its rating data.
Description: Nominal motor power factor (cosPhi) from rating plate - see P0304.
Dependency: Changeable only when P0010 = 1 (quick commissioning).
Visible only when P0100 = 0 or 2, (motor power entered in [kW]).
Setting 0 causes internal calculation of value. The value is displayed in r0332.
Description: Nominal motor efficiency in [%] from rating plate - see P0304.
Dependency: Changeable only when P0010 = 1 (quick commissioning).
Visible only when P0100 = 1, (i.e. motor power entered in [hp]).
Setting 0 causes internal calculation of value. The value is displayed in r0332.
Description: Nominal motor frequency [Hz] from rating plate - see P0304.
Dependency: Changeable only when P0010 = 1 (quick commissioning).
Pole pair number recalculated automatically if parameter is changed.
Note: Changes to P0310 can influence the maximum motor frequency. For further information see P1082.
p0307[0...2] Rated motor power / Rated motor power
Access level: 1 P-Group: Motor Data type: Floating Point
Quick comm. YES Active: NO Data set: DDS
Can be changed: C
Min Max Factory setting
0.01 2000.00 0.75
p0308[0...2] Rated motor cosPhi / Rated mot. cosPhi
Access level: 1 P-Group: Motor Data type: Floating Point
Quick comm. YES Active: NO Data set: DDS
Can be changed: C
Min Max Factory setting
0.000 1.000 0.000
p0309[0...2] Rated motor efficiency / Rated efficiency
Access level: 1 P-Group: Motor Data type: Floating Point
Quick comm. YES Active: NO Data set: DDS
Can be changed: C
Min Max Factory setting
0.0 [%] 99.9 [%] 0.0 [%]
p0310[0...2] Rated motor frequency / Rated motor freq.
Access level: 1 P-Group: Motor Data type: Floating Point
Quick comm. YES Active: NO Data set: DDS
Can be changed: C
Min Max Factory setting
12.00 [Hz] 650.00 [Hz] 50.00 [Hz]