Parameters
List of Parameters
1-50
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Stator resistance value in [Ohms] for connected motor (line value).
The parameter value doesn't include the cable resistance.
There are three ways to determine the value for this parameter:
1. Calculate using
- P0340 = 1 (data entered from rating plate) or
- P0010 = 1, P3900 = 1, 2 or 3 (end of quick commissioning).
2. Measure using P1900 = 2 (standard motor data identification - value for stator resistance is overwritten).
Measure using P1900 = 3 (compleate motor data identification - same like setting 2; additional detection of the
saturation curve)
3. Measure manually using an Ohmmeter.
Note: Since the manually measured resistor is a line-to-line value, which includes the cable resistors, the measured value
has to be divided by two and the cable resistor of a line has to be subtracted from that value.
The value entered in P0350 (stator resistance) is the one obtained by the method last used.
Default value is depending on inverter type and its rating data.
Description: Describes cable resistance between inverter and motor for one phase.
The value corresponds to the resistance of the cable between the inverter and the motor, relative to the rated
impedance.
Description: Sets rotor resistance of motor equivalent circuit (phase value).
Dependency: Calculated automatically using the motor model or determined using P1900 (motor identification).
Description: Sets stator leakage inductance [mH] of motor equivalent circuit (phase value).
Dependency: Calculated automatically using the motor model or determined using P1900 (motor identification).
p0350[0...2] Stator resistance (line) / Stator res. (L)
Access level: 3 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00001 [Ohm] 2000.00000 [Ohm] 2.00000 [Ohm]
p0352[0...2] Cable resistance / Cable resistance
Access level: 3 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [Ohm] 120.0 [Ohm] 0.0 [Ohm]
p0354[0...2] Rotor resistance / Rotor resistance
Access level: 3 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [Ohm] 300.0 [Ohm] 10.0 [Ohm]
p0356[0...2] Stator leakage inductance / Stator leak.induct
Access level: 3 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00001 1000.00000 10.00000

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals