List of Parameters
Parameters
1-19
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets the store mode for parameters.
The store mode can be configured for all interfaces listed under "Index".
Values: 0: Volatile (RAM)
1: Nonvolatile (EEPROM)
Index: [0] = USS on RS485
[1] = USS on RS232
[2] = Fieldbus
Note: An independent store request may be part of the serial communications (e.g. PKE bits 15-12 of USS protocol), set
by a PLC or PC tools like STARTER. See the table below for an influence on the settings of P0014.
1. With the BOP the parameter will always be stored in the EEPROM.
2. P0014 itself will always be stored in the EEPROM.
3. P0014 will not be changed by performing a factory reset (P0010 = 30 and P0970 = 1).
4. P0014 can be transferred during a download (P0010 = 29).
When transferring parameter p0014, the inverter uses its processor to carry-out internal calculations. Communica-
tions - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to make these calculations.
This can result in the following error messages at the connected SIMATIC S7 control (communications via fieldbus):
• Parameter fault 30
• Drive fault 70
• Drive fault 75
When using STARTER (USS) to commission the drive system, data cannot be entered while these calculations are
being made.
The faults can be acknowledged as soon as the calculations have been completed in the frequency inverter. These
calculations can take up to one minute to complete.
Description: Displays version number of installed firmware.
p0014[0...2] Store mode / Store mode
Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
0 1 0
Store request via USS/PROFIBUS
EEPROM
Value of p0014[x] Result
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
RAM
RAM
RAM
RAMRAM
r0018 Firmware version / Firmware version
Access level: 1 P-Group: Converter Data type: Floating Point
Unit: - Data set: -