EasyManuals Logo

Siemens CU240S DP-F Parameter Manual

Siemens CU240S DP-F
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #194 background imageLoading...
Page #194 background image
Parameters
List of Parameters
1-194
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Specifies reference voltage for generation of a test voltage vector (e.g. used for shunt calibration). [V]
Description: Defines phase of voltage vector
1: u-axis
2: v-axis
3: w-axis
4: -u-axis
5: -v-axis
6: -w-axis
7: uv-axis (30°)
8: wu-axis (150°)
9: vw-axis (270°)
10: -uv-axis (210°)
11: -wu-axis (330°)
12: -vw-axis (90°)
p1930 Voltage setpoint for calibration / Volt setp. calibr.
Access level: 4 P-Group: Motor identification Data type: Floating Point
Quick comm. NO Active: YES Data set: -
Can be changed: U, T
Min Max Factory setting
0 [V] 1000 [V] 0 [V]
p1931 Phase / Phase
Access level: 4 P-Group: Motor identification Data type: Unsigned16
Quick comm. NO Active: YES Data set: -
Can be changed: U, T
Min Max Factory setting
1 12 1

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals